PVC Copper Instrumentation Cable 6-20

PVC Copper Instrumentation Cable

Individual and Overall Shield

TE Wire & Cable Copper Instrumentation Cables are designed for use in NEC Article 725 Class 1 Division 2 Hazardous Location and comply with NEC 725 for use in Class 2 and Class 2 Circuits. XLPE, TPE and LSZH insulation option available.  Cables with up to 50 pairs and continuous lengths of 5000-10,000 FT are possible. TE Wire & Cable conductor sizes, insulations, jackets and armors can be mixed and matched to custom design a cable for specific application.

PVC twisted individual and overall shielded instrumentation cable is ideal for systems sensitive to induced voltage and electrical noise. The twisting of the conductor and the Aluminum/polyester taper shield provides protection against cross talk, static and magnetic noise in instrumentation circuits. Conductors are insulated with color-coded PVC, then twisted and shielded with individual tin/copper drain wire. Next, an Aluminum Mylar tape is wrapped around the wires with a tin/copper drain wire, followed by a final layer of overall PVC jacket. The wire is UL listed for Power Limited Tray Cable (PLTC) 300V applications.

Applications
Available Options
Features
Specifications
Ordering Code
    • New Plant Constructions
    • Utilities and Industrial Plants
    • Petrochemical Plants
    • Testing Rig set up
    • Instrumentation Circuits
    • For use in NEC Article 725 Class 1 Division 2 Hazardous Locations
    • Complies with NEC 725 for use in Class 2 and Class 3 Circuits
    • Metal Overbraid
    • SWA Armor (20 AWG & larger)
    • Metal Bond Continuous Barrier
    • Sunlight Resistant
    • Passes IEEE 383 Flame Test
    • Passes VW-1 Flame Test
    • Available as type ITC
    • CPE and TPE Constructions are also available
    • Special Color Codes
    • Continuous use up to 221F (105C) 300 Volt
    • Flame Retardant
    • Good Moisture, Chemical and Solvent  Resistance
    • 100% Continuous Drain/Shield Contact
    • PVC/PVC provides economical construction
  • Conductors: Solid or stranded, bare or tinned copper

    Insulation: Nominal .016″ (.40mm) flame retardant PVC

    Color Code: Pairs-black & white, numbered. Triads-black, white & red, numbered (other colors available)

    Construction: Twisted pairs or triads

    Individual Shield: .00135″ (.03mm) aluminum/polyester tape, 25% overlap

    Pair Drain Wire: 7-strand tinned copper, 2 AWG sizes smaller than cable drain wire

    Communication Wire (Optional): 22 AWG (.61mm) 7-strand copper insulated with nominal .015″ (.38mm) orange PVC ( used in constructions 4 pair/triad and larger)

    Cable Shield: .002″(.05mm) aluminium/polyester tape, 25% overlap

    Cable Drain Wire: 7-strand tinned copper, 2 AWG sizes smaller than conductor

    Outer Jacket: Flame retardant extruded PVC with nylon ripcord under jacket

    Operating Temperature: -15F (-26C) to +221F (+105C) continuous

  • UP/ALM/ALPTWK – [( 1 )] – [( 2 )] [( 3 )] – [( 4 – 5 )]

    1) # of Pairs/ Triads

    From 2 to 50 pair/triad (contact for larger pair counts)

    2) Wire Size AWG

    Available from 12 to 22 AWG

    3) Add (F) for Stranded Wire

    Example: 20F = 20 AWG 7-Strand Conductor

    4) Pair or Triad Designation

    Triad – 3 conductor- black, white & red, numbered

    BX – 2 conductor per – black & white, numbered

    5) TIN Copper OPTION

    Option: Add (TIN) to the end of Ordering code to specify tinned copper conductors.